General
Column installed insulation load switch, type RPS-12/27/38-20,is suitable for the rated voltage 12/27/38kV,rated current 400A,630A,50/60Hz power grid open circuit,load current in closed Power system,overload curren. This load switch can separate those broken distribution line automatically.
With the latest technology, it has the newest electronic controller.The switch can be used by manual operation, electric operation and operation from a long distance. Electronic controller is installed in a stainless steel cabinet which is suitable for using under all kinds of climatic conditions. In addition, there are some wired and wireless modem installed in the cabinet through which it can realize the remote monitoring and control. Simple installation on column is convenient, fast, and also can reduce the construction cost.
Main technical specifications
No. | Name | Unit | RPS-12 | RPS-27 | RPS-38 | |
1 | Rated voltage | kV | 12 | 27 | 38 | |
2 | Rated frequency | Hz | 50/60 | 50/60 | 50/60 | |
3 | Lightning impulse withstand voltage | relatively | kV | 75 | 125 | 185 |
Fracture | 85 | 145 | 215 | |||
Power frequency withstand voltage 1min |
relatively | kV | 42 | 64 | 95 | |
Fracture | 50 | 79 | 110 | |||
5 | Rated current | A | 630(400) | 630(400) | 630(400) | |
6 | Rated breaking load current (0.07Mpa / 20 ° C) | A | 630(400) | 630(400) | 630(400) | |
7 | breaking current under zero gauge pressure | A | 630(400) | 630(400) | 630(400) | |
8 | peak withstand current | kA | 50 | 50 | 50 | |
9 | Rated short time making current | kA | 50 | 50 | 50 | |
11 | rated short time withstand current | KA/s | 20/4 | 20/4 | 20/4 | |
12 | rated cable charging breaking current | A | 25 | 25 | 25 | |
13 | rated line charging breaking current | A | 16 | 16 | 16 | |
14 | rated closed-loop breaking current | A | 630(400) | 630(400) | 630(400) | |
15 | exciting current | A | 21 | 21 | 21 | |
16 | rated current breaking times | Times | ≥400 | ≥400 | ≥400 | |
17 | rated working pressure | MPa | 0.07 | 0.07 | 0.25 | |
20 | operation of echanical stability | times | 6000 | 6000 | 6000 | |
21 | rated operating voltage and auxiliary circuits rated voltage | V | DC 220/ 110/48/24 |
DC 220/ 110/48/24 |
DC 220/ 110/48/24 |
|