Customization: | Available |
---|---|
Breaking Capacity: | High Voltage Circuit Breakers |
Operation: | Electric Type |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
No. | Item | Unit | Data |
1 | Rated voltage | KV | 145 |
2 | Rated frequency | Hz | 50/60 |
3 | Rated current | A | 3150 |
4 | 1min power frequency withstand voltage | KV | 265 |
5 | Lingthning impluse withstand voltage(peak value | KV | 650 |
6 | 5 min power frequency voltage at zero gas pressure | KV | 109 |
7 | Rated short circuit breaking current | KA | 80...100 |
8 | Rated out-of-phase breaking current | KA | 10 |
9 | Rated cable(line) charging breaking current(peak) | A | 50 |
10 | Rated gas pressure | MPa | 0.5 |
11 | Main loop resistance | uΩ | ≤45 |
12 | Operation sequence | O-0.3s-CO-180s-CO | |
13 | SF6 gas leakage rate(per year) | % | ≤1 |
14 | Moisture content(V/V) | ppm | ≤150 |
15 | Across the open contacts | mm | ≥3950 |
Creepage distance | |||
TO earth | ≥3950 | ||
16 | Mechanical life | times | 10,000 |