Customization: | Available |
---|---|
Breaking Capacity: | High Voltage Circuit Breakers |
Operation: | Energy-storage Type |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
General characteristics of fixed circuit-breakers (12-17.5-24kV) |
![]() |
Circuit-breaker | VM1 12 | |||||||||||||
Standards | IEC 62271-100 | · | ||||||||||||
CEI 17-1(file 1375) | · | |||||||||||||
Rated voltage Ur(Kv) | 12 | |||||||||||||
Rated insulation voltage Us(Kv) | 12 | |||||||||||||
Withstand voltage at 50Hz Ud(1min)(kV) | 28 | |||||||||||||
Impulse withstand voltage Up(Kv) | 75 | |||||||||||||
Rated frequency fr(Hz) | 50-60 | |||||||||||||
Rated normal current (40ºC) Ir(A) | 630 | 630 | 1250 | 1250 | 1600 | 1600 | 2000 | 2000 | 2500 | |||||
Rated breaking capacity(rated symmetrical short-circuit current) Isc(Ka) | 16 | 16 | 16 | 16 | - | - | - | - | - | |||||
20 | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 20 | ||||||
25 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | ||||||
31.5 | 31.5 | 31.5 | 31.5 | 31.5 | 31.5 | 31.5 | 31.5 | 31.5 | ||||||
Rated short-time withstand current (3s) Ik(Ka) | 16 | 16 | 16 | 16 | - | - | - | - | - | |||||
20 | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 20 | ||||||
25 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | ||||||
31.5 | 31.5 | 31.5 | 31.5 | 31.5 | 31.5 | 31.5 | 31.5 | 31.5 | ||||||
Making capacity Ip(Ka) | 40 | 40 | 40 | 40 | - | - | - | - | - | |||||
50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | ||||||
63 | 63 | 63 | 63 | 63 | 63 | 63 | 63 | 63 | ||||||
80 | 80 | 80 | 80 | 80 | 80 | 80 | 80 | 80 | ||||||
Operating sequence (O-0.3s-CO-3min-CO) | · | |||||||||||||
Opening time (ms) | 35…45 | |||||||||||||
Acr time (ms) | 10…15 | |||||||||||||
Total interruption time (ms) | 45…60 | |||||||||||||
Closing time(ms) | 50…60 | |||||||||||||
Mechanical operations(cycles) | Actuator | …100,000 | ||||||||||||
interrupters | …30,000 | |||||||||||||
Electrical operations(cycles) | Rated current | …30,000 | ||||||||||||
Under short-circuit | …50 | |||||||||||||
Maximum overall dimensions | H(mm) | 475 | 475 | 475 | 475 | 599 | 599 | 599 | 599 | 616 | ||||
W(mm) | 450 | 570 | 450 | 570 | 570 | 700 | 570 | 700 | 700 | |||||
D(mm) | 424 | 424 | 424 | 424 | 424 | 424 | 424 | 424 | 424 | |||||
Pole centre distance | I(mm) | 150 | 210 | 150 | 210 | 210 | 275 | 210 | 275 | 275 | ||||
weight | ≤25Ka(kg) | 94 | 98 | 94 | 98 | 130 | 135 | 130 | 135 | 135 | ||||
31.5Ka(kg) | 101 | 105 | 101 | 105 | 130 | 135 | 130 | 135 | 135 | |||||
Standardised table of dimensions 1VCD | 00001 | 00002 | 00001 | 00002 | 00003 | 00004 | 00003 | 00004 | 00004 | |||||
Operating temperature (ºC) | -25…+40 | |||||||||||||
tropicalisation | IEC:60068-2-30 | · | ||||||||||||
721-2-1 | · | |||||||||||||
Electromagnetic compatibility IEC 60694 | · | |||||||||||||
(1)the circuit-breakers up to 17.5Kv -1250A-31.5Ka, are made with polyamide poles. |
Circuit-breaker | VM1 17 | |||||||||||||
Standards | IEC 62271-100 | · | ||||||||||||
CEI 17-1(file 1375) | · | |||||||||||||
Rated voltage Ur(Kv) | 17.5 | |||||||||||||
Rated insulation voltage Us(Kv) | 17.5 | |||||||||||||
Withstand voltage at 50Hz Ud(1min)(kV) | 38 | |||||||||||||
Impulse withstand voltage Up(Kv) | 95 | |||||||||||||
Rated frequency fr(Hz) | 50-60 | |||||||||||||
Rated normal current (40ºC) Ir(A) | 630 | 630 | 1250 | 1250 | 1600 | 1600 | 2000 | 2000 | 2500 | |||||
Rated breaking capacity(rated symmetrical short-circuit current) Isc(Ka) | 16 | 16 | 16 | 16 | - | - | - | - | - | |||||
20 | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 20 | ||||||
25 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | ||||||
31.5 | 31.5 | 31.5 | 31.5 | 31.5 | 31.5 | 31.5 | 31.5 | 31.5 | ||||||
Rated short-time withstand current (3s) Ik(Ka) | 16 | 16 | 16 | 16 | - | - | - | - | - | |||||
20 | 20 | 20 | 20 | 20 | 20 | 20 | 20 | 20 | ||||||
25 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | ||||||
31.5 | 31.5 | 31.5 | 31.5 | 31.5 | 31.5 | 31.5 | 31.5 | 31.5 | ||||||
Making capacity Ip(Ka) | 40 | 40 | 40 | 40 | - | - | - | - | - | |||||
50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | ||||||
63 | 63 | 63 | 63 | 63 | 63 | 63 | 63 | 63 | ||||||
80 | 80 | 80 | 80 | 80 | 80 | 80 | 80 | 80 | ||||||
Operating sequence (O-0.3s-CO-3min-CO) | · | |||||||||||||
Opening time (ms) | 35…45 | |||||||||||||
Acr time (ms) | 10…15 | |||||||||||||
Total interruption time (ms) | 45..60 | |||||||||||||
Closing time(ms) | 50…60 | |||||||||||||
Mechanical operations(cycles) | Actuator | …100,000 | ||||||||||||
interrupters | …30,000 | |||||||||||||
Electrical operations(cycles) | Rated current | …30,000 | ||||||||||||
Under short-circuit | …50 | |||||||||||||
Maximum overall dimensions | H(mm) | 475 | 475 | 475 | 475 | 599 | 599 | 599 | 599 | 616 | ||||
W(mm) | 450 | 570 | 450 | 570 | 570 | 700 | 570 | 700 | 700 | |||||
D(mm) | 424 | 424 | 424 | 424 | 424 | 424 | 424 | 424 | 424 | |||||
Pole centre distance | I(mm) | 150 | 210 | 150 | 210 | 210 | 275 | 210 | 275 | 275 | ||||
weight | ≤25Ka(kg) | 94 | 98 | 94 | 98 | 130 | 135 | 130 | 135 | 135 | ||||
31.5Ka(kg) | 101 | 105 | 101 | 105 | 130 | 135 | 130 | 135 | 135 | |||||
Standardised table of dimensions 1VCD | 00001 | 00002 | 00001 | 00002 | 00003 | 00004 | 00003 | 00004 | 00004 | |||||
Operating temperature (ºC) | ||||||||||||||
tropicalisation | IEC:60068-2-30 | · | ||||||||||||
721-2-1 | · | |||||||||||||
Electromagnetic compatibility IEC 60694 | · | |||||||||||||
(1)the circuit-breakers up to 17.5Kv -1250A-31.5Ka, are made with polyamide poles. |
Circuit-breaker | VM1 24 | |||||||||||
Standards | IEC 62271-100 | · | ||||||||||
CEI 17-1(file 1375) | · | |||||||||||
Rated voltage Ur(Kv) | 24 | |||||||||||
Rated insulation voltage Us(Kv) | 24 | |||||||||||
Withstand voltage at 50Hz Ud(1min)(kV) | 50 | |||||||||||
Impulse withstand voltage Up(Kv) | 125 | |||||||||||
Rated frequency fr(Hz) | 50-60 | |||||||||||
Rated normal current (40ºC) Ir(A) | 630 | 630 | 1250 | 1250 | 1600 | 2000 | 2500 | |||||
Rated breaking capacity(rated symmetrical short-circuit current) Isc(Ka) | 16 | 16 | 16 | 16 | 16 | 16 | - | |||||
20 | 20 | 20 | 20 | 20 | 20 | - | ||||||
25 | 25 | 25 | 25 | 25 | 25 | 25 | ||||||
- | - | - | - | - | - | - | ||||||
Rated short-time withstand current (3s) Ik(Ka) | 16 | 16 | 16 | 16 | 16 | 16 | - | |||||
20 | 20 | 20 | 20 | 20 | 20 | - | ||||||
25 | 25 | 25 | 25 | 25 | 25 | 25 | ||||||
- | - | - | - | - | - | - | ||||||
Making capacity Ip(Ka) | 40 | 40 | 40 | 40 | 40 | 40 | - | |||||
50 | 50 | 50 | 50 | 50 | 50 | - | ||||||
63 | 63 | 63 | 63 | 63 | 63 | 63 | ||||||
- | - | - | - | - | - | - | ||||||
Operating sequence (O-0.3s-CO-3min-CO) | · | |||||||||||
Opening time (ms) | 35…45 | |||||||||||
Acr time (ms) | 10…15 | |||||||||||
Total interruption time (ms) | 45..60 | |||||||||||
Closing time(ms) | 50…60 | |||||||||||
Mechanical operations(cycles) | Actuator | …100,000 | ||||||||||
interrupters | …30,000 | |||||||||||
Electrical operations(cycles) | Rated current | …30,000 | ||||||||||
Under short-circuit | …50 | |||||||||||
Maximum overall dimensions | H(mm) | 631 | 631 | 631 | 631 | 642 | 642 | 661 | ||||
W(mm) | 570 | 700 | 570 | 700 | 700 | 700 | 700 | |||||
D(mm) | 424 | 424 | 424 | 424 | 424 | 424 | 424 | |||||
Pole centre distance | I(mm) | 210 | 275 | 210 | 275 | 275 | 275 | 275 | ||||
weight | ≤25Ka(kg) | 108 | 115 | 108 | 115 | 137 | 137 | 137 | ||||
31.5Ka(kg) | - | - | - | - | - | - | - | |||||
Standardised table of dimensions 1VCD | 00005 | 00006 | 00005 | 00006 | 00007 | 00007 | 00007 | |||||
Operating temperature (ºC) | -25…+40 | |||||||||||
tropicalisation | IEC:60068-2-30 | · | ||||||||||
721-2-1 | · | |||||||||||
Electromagnetic compatibility IEC 60694 | · | |||||||||||
(1)the circuit-breakers up to 17.5Kv -1250A-31.5Ka, are made with polyamide poles. |