Customization: | Available |
---|---|
Certification: | ISO9001 |
Shell Material: | Aluminum Alloy |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
C - Cable switch module | F - Cable switch module | V - Cable switch module |
D - Direct cable connection module | De - Direct cable connection module with earthing switch | M - Metering module |
iSafering outer assembly |
Upper front cover 1. Manometer 2. Nameplate module 3. Short circuit indicator 4. Capacitive voltage indication 5. Load break / earthing switch position indicator 6. Push buttons close/open operation 7. Charged spring indicator 8. Self-powered protection relay 9. Vacuum circuit-breaker position 10. Operation shaft 11. Padlock device Lower front cover 12. Nameplate switchgear 13. Fuse blown indicator 14. Disconnector / earthing switch position indicator 15. Capacitive voltage indication Cable compartment cover 16. Cable compartment cover standard 17. Cable compartment cover with inspection window 18. Support bar (removable) Side cover 19. Lifting lug 20. Operating handle (standard on right hand side) |
|
1. Mechanism compartment 2. SF6 gas tank 3. Cable compartment 4. Pressure relief area |
SafeRing | C-module | F-module | V-module | ||||
Switch disconnector | Earthing switch | Switch-fuse disconnector | Downstream earthing switch | Vacuum circuit-breaker | Earthing switch/ disconnector | ||
Rated voltage | Kv | 12/17,5/24 | 12/17,5/24 | 12/17,5/24 | 12/17,5/24 | 12/17,5/24 | 12/17,5/24 |
Rated frequency 5) | Hz | 50/50/50 | 50/50/50 | 50/50/50 | 50/50/50 | 50/50/50 | 50/50/50 |
Power frequency withstand voltage | kV | 28/38/50 | 28/38/50 | 28/38/50 | 28/38/50 | 28/38/50 | 28/38/50 |
Lightning impulse withstand voltage | kV | 95/95/125 | 95/95/125 | 95/95/125 | 95/95/125 | 95/95/125 | 95/95/125 |
Rated normal current | A | 630/630/630 | 2001) | 200/200/200 | |||
Breaking capacities: | |||||||
active load | A | 630/630/630 | |||||
closed loop | A | 650/650/650 | |||||
off load cable charging | A | 140/140/140 | |||||
off load transformer | A | 20/20/20 | |||||
earth-fault | A | 205/160/160 | |||||
earth-fault cable charging | A | 117/91/91 | |||||
short-circuit breaking current | kV | see2) | 16/16/16 | ||||
Making capacity | kV | 52,5/40/40 | 52,5/40/40 | see2) | 12,5/12,5/12,5 | 40/40/40 | 40/40/40 |
Short time current 3 sec. 3) | kV | 21/16/16 | 21/16/16 | 16/16/16 | 16/16/16 |