Customization: | Available |
---|---|
Breaking Capacity: | High Voltage Circuit Breakers |
Operation: | Electric Type |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
No. | Item | Unit | Data | ||
1.
|
Rated voltage | KV | 12/24/36/40.5 | ||
2.
|
Power frequency | Wet | 42/65/70/95 | ||
dry | 45/70/80/110 | ||||
3.
|
Lingthning impluse withstand voltage(peak value) | 75/95/125/150/170/185/200 | |||
4.
|
Rated current | A | 630/1250A/1600/2000/2500A | ||
5.
|
Rated short circuit breaking current | KA | 25/31.5/40 | ||
6.
|
Rated capacitor bank breaking current | A | 600/800 | ||
7.
|
Rated short circuit breaking times | Times | 30 | ||
8.
|
Rated making current | KA | 63/80/100 | ||
9.
|
Rated short circuit peak withsatnd current | ||||
10.
|
Rated shortcircuit withstand curren | 25/31.5/40 | |||
11.
|
Rated short time duration time | S | 3/4 | ||
12.
|
Complete breaking time | ms | ≤100 | ||
13.
|
Opening time | Highest operate voltage | 15~50 | ||
Rated operate voltage | 15~50 | ||||
Lowest operate voltage | 30~60 | ||||
14.
|
Closing time | 25~50 | |||
15.
|
Contact closing bounce time | ≤3 | |||
Out of simultaneity of contact switching | ≤2 | ||||
Contact overitravel on Opening | mm | ≤2 | |||
16.
|
Mechanical life | 20000(Normal) | |||
17.
|
Electrical life(Rated onload switching) | 10000(Noraml) | |||
18.
|
Rated operate sequence | O-0.3-CO-180S-CO | |||
19.
|
Weight | ≤250kg |