Customization: | Available |
---|---|
Breaking Capacity: | High Voltage Circuit Breakers |
Operation: | Electric Type |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
A) Open/closed auxiliary contacts B) Geared motor for closing spring charging C) Built-in closing spring charging lever D) Mechanical signalling device for circuit-breaker open/closed E) Mechanical operation counter F) Plug-socket connectors of electrical accessories in the truck G) Signalling device for closing springs charged/discharged |
H) Service releases I) Closing pushbutton L) Opening pushbutton M) Operating mechanism locking electromagnet N) Additional shunt opening release O) Transient contact P) Contacts for signalling spring charged/discharged |
Circuit-breaker | VD4 | ||||
Rated voltage | Ur [kV] | 12 | 17.5 | 24 | 36 |
Rated insulation voltage | Us [kV] | 12 | 17.5 | 24 | 36 |
Withstand voltage at 50Hz | Ud (1min) [kV] | 28 | 38 | 50 | 70 |
Impulse withstand voltage | Up [kV] | 75 | 95 | 125 | 170 |
Rated frequency | fr [Hz] | 50-60 | |||
Rated normal current(40ºC) | Ir [A] | 630 / 1250 / 1600 / 2000 / 2500 / 3150 / 4000 | |||
Rated breaking capacity (rated symmetrical short-circuit current) | Isc [kA] | 25 / 31.5 / 40 | |||
Rated short-time withstand current(4s) | Ik [kA] | 25 / 31.5 / 40 | |||
Making capacity | Ip [kA] | 63 / 80 / 100 | |||
Operation sequence | [O-0.3s-CO-15s-CO] | ||||
Opening time | [ms] | 40...60 | |||
Arcing time | [ms] | 10...15 | |||
Total breaking time | [ms] | 50...75 | |||
Closing time | [ms] | 50...80 | |||
Operating temperature | [ºC] | 15 ... +40 |