HD4 Gas Insulated Mv Circuit-Breakers up to: 40.5kv 3600A 50ka

Breaking Capacity: High Voltage Circuit Breakers
Operation: Electric Type
Speed: Normal Type Circuit Breaker
Arc-extinguishing Medium: SF6
Installation: Fixed
Structure: Vcb
Customization:

Contact Supplier

Diamond Member Since 2013

Suppliers with verified business licenses

Manufacturer/Factory & Trading Company

Basic Info.

Model NO.
HD4
Poles Number
3
Type
Circuit Breaker
Function
Overcurrent Protection
Certification
ISO9001-2000
Transport Package
Wooden Case
Specification
IEC, GB
Trademark
Rockwill
Origin
China
HS Code
8535210000
Production Capacity
1000PCS

Product Description

Medium voltage products
HD4
Gas insulated MV circuit-breakers up to:40.5kV;3600A;50kA
 
Description


General information

HD4 medium voltage circuit-breakers use sulphur hexafluoride gas(SF6) to extinguish the electric arc and as the insulating medium.

Breaking in SF6 gas takes place without any arc chopping and without generation of over voltages. These characteristics ensure long electrical life of the circuit-breaker and limited dynamic, dielectric and thermal stresses on the installation. The circuit-breaker poles, which make up the breaking part, are systems with lifelong sealed pressure(IEC 62271-100 standards) and are maintenance-free.

The ESH type mechanical operating mechanism, with stored energy has free release and allows opening and closing operations independently of the operator's actions.

The operating mechanism and the poles are fixed to the metal structure which also acts as a support for the kinetics for operating the moving contacts.

Circuit-breakers in the withdrawable version are fitted with a truck to allow racking in and racking in and racking out of the switchgear or enclosure. 

The light and compact structure of the circuit-breaker ensures great sturdiness and excellent mechanical reliability.

Available versions

HD4 circuit-breakers are available in the fixed and withdrawable version with front operating mechanism. The withdrawable version is available for powercube modules and unigear type ZS1,ZS2,ZS3.2 switchgears.

Fields of application

HD4 circuit-breakers are used in power distribution to control and protect lines, transformer and distribution substations, motors, transformers, capacitor banks, etc.

Thanks to the SF6 autopuffer breaking technique, the HD4 circuit-breakers do not generate operating overvoltages, and are therefore also highly suitable for retrofitting, upgrading and enlarging older installations where the motor, cable, etc. insulating materials may be particularly sensitive to dielectric stresses.

Circuit-breaker operating mechanism
 HD4 Gas Insulated Mv Circuit-Breakers up to: 40.5kv 3600A 50ka
  1. Gas monitoring device with led
  2. Opening pushbutton
  3. Mechanical undervoltage override
  4. Undervoltage release
  5. Service releases(opening and closing)
  6. Operating mechanism locking electromagnet
  7. Closing pushbutton
  8. Open/closed auxiliary contacts
  9. Protection circuit-breaker for closing spring loading motor
  1. Lock that prevents racking-in when door is open
  2. Mechanical operation counter
  3. Pressure switch
  4. Mechanical signaling device for circuit-breaker open/closed
  5. Key lock removed when circuit-breaker is open 
  6. Contacts for signaling spring charged/discharged
  7. Signaling device for closing springs charged/didcharged
  8. Closing spring loading motor limit switch
  9. Geared motor for closing spring charging

General characteristics of fixed circuit-breakers(17.5kV)
Circuit-breaker HD4 17
Standards IEC62271-100 ·
Rated voltage  Ur(kV) 17.5
Rated insulation voltage  Us(kV) 17.5
Withstand voltage at 50Hz Ud(1min)(kV) 38
Impulse withstand voltage Up(kV) 95
Rated frequency fr(Hz) 50-60
Rated normal current(40ºC)(1) Ir(A) 630 1250 1600 2000 2500 3150 3600
Rated breaking capacity Isc(kA) 16 16 - - - - -
- - - - - - -
25 25 - 25 25 25 25
31.5 31.5 - 31.5 31.5 31.5 31.5
- - 40 40 40 40 40
- - 50 50 50 50 50
Rated short-time withstand current(3 s) IK(KA) 16 16 - - - - -
- - - - - - -
25 25 - 25 25 25 25
31.5 31.5 - 31.5 31.5 31.5 31.5
- - 40 40 40 40 40
- - 50 50 50 50 50
Making capacity Ip(kA) 40 40 - - - - -
50 50 - - - - -
- - - 63 63 63 63
80 80 - 80 80 80 80
- - 100 100 100 100 100
- - 125 125 125 125 125
Operation sequence (O-0.3s-CO-15s-CO) ·
Opening time (ms) 35-60
Acring time(ms) 10-15
Total breaking time (ms) 55-60
Closing time (ms) 85
Overall dimensions  HD4 Gas Insulated Mv Circuit-Breakers up to: 40.5kv 3600A 50ka H(mm) 623 655 655
W(mm) 618 618 730
D(mm) 446 561 603
Pole centre distance(mm) 210 210 275
Weight  (kg) 114 145 165
Standardized table of dimensions 1VCD000231 TN 163 TN 7165
Absolute SF6 gas pressure(2)  (kPa) 380(430 to 31.5kA) 380 380
Operating temperature (ºC) -5+40ºC
Tropicalization IEC:60068-2-30,60721-2-1 ·
Electromagnetic compatibility  IEC 62271-1 ·
  1. rated normal current defined in free air.
  2. Rated service value.
  3. Including insulating shields(available on request).
General characteristics of fixed circuit-breakers(24Kv)
Circuit-breaker HD4 24
Standards  EC62271-100 ·
Rated voltage Ur(kv) 24
Rated insulation voltage Us(Kv) 24
Withstand voltage at 50Hz Ud(1 min)(kV) 50
Impulse withstand voltage Up(kV) 125
Rated frequency fr(Hz) 50-60
Rated normal current(40ºC)(1) Ir(A) 630 1250 630 1250 1600 2000 2500 3150 3600
Rated breaking capacity Isc(kA) 16 16 16 16 - - - - -
20 20 20 20 - - - - -
25 25 25 25 25 25 25 25 25
- - - - 31.5 31.5 31.5 31.5 31.5
- - - - 40 40 40 40 40
- - - - - - - - -
Rated short-time withstand current(3s) Ik(kA) 16 16 16 16 - - - - -
20 20 20 20 - - - - -
25 25 25 25 25 25 25 25 25
- - - - 31.5 31.5 31.5 31.5 31.5
- - - - 40 40 40 40 40
- - - - - - - - -
Making capacity Ip  (kA) 40 40 40 40 - - - - -
50 50 50 50 - - - - -
63 63 63 63 63 63 63 63 63
- - - - 80 80 80 80 80
- - - - 100 100 100 100 100
- - - - - - - - -
Operation sequence (O-0.3s-CO-15s-CO) ·
Opening time  (ms) 35-60
Arcing time  (ms) 10-15
Total breaking time (ms) 55-60
Closing time (ms) ≤85
Overall dimensions  HD4 Gas Insulated Mv Circuit-Breakers up to: 40.5kv 3600A 50ka H(mm) 818 730 655 818(3)
W(mm) 618 748 730 730
D(mm) 600 496 561 620(3)
Pole centre distance I(mm) 210 275 275 275
Weight (Kg) 119 119 145 165
Standardized table of dimensions 1VCD000235 1VCD000237 TN 7174 TN 7165
Absolute SF6 gas pressure(2) (kPa) 380 380(480 to 25kA and 40 kA)
Operating temperature (ºC) -5+40ºC
Tropicalization IEC:60068-2-30,60721-2-1 ·
Electromagnetic compatibility IEC62271-1 ·

General characteristics of fixed circuit-breakes(36kV)
 
Circuit-breaker HD4 36 HD4 36
Standards IEC62271-100 · ·
Rated voltage Ur(kV) 36 36
Rated insulation voltage Us(kV) 36 36
Withstand voltage at 50Hz Ud(1 min)(kV) 70 70
Impulse withstand voltage Up(kV) 170 170
Rated frequency fr(Hz) 50-60 50-60
Rated normal current(40ºC)(1)    Ir(A) 630 1250 1600 1250(3) 1600(3) 2000(3) 2500(3)
Rated breaking capacity Isc(kA) 16 16 16 - - - -
20(5) 20(5) 20(5) - - 20 20
- - - 25 25 25 25
- - - 31.5 31.5 31.5 31.5
Rated short-time withstand current(3s) Ik(kA) 16 16 16 - - - -
20 20 20 - - 20 20
- - - 25 25 25 25
- - - 31.5 31.5 31.5 31.5
Making capacity Ip(kA) 40 40 40 - - - -
50 50 50 - - - -
- - - 63 63 63 63
- - - 80 80 80 80
Operation sequence (O-0.3s-CO-15s-CO)              
(O-0.3s-CO-3min-CO) · · · · · · ·
Opening time (ms) 45 45
Arcing time (ms) 10-15 10-15
Total breaking time (ms) 55-60 55-60
Closing time (ms) 80 80
Maximum overall dimensions without insulating screens between phases(4) HD4 Gas Insulated Mv Circuit-Breakers up to: 40.5kv 3600A 50ka
 
H(mm) 730/1060(6) 790/1123(6) 790/1123(6)
W(mm) 880/955(6) 748/805(6) 748/805(6)
D(mm) 695 833 833
Pole centre distance I(mm) 350 275 275
Weight (kg) 124 128 128 175 175 180 190
Standardized table of dimensions TN 7241 TN 7268 TN 7315
Absolute SF6 gas pressure (kPa) 380 450 450
Operating temperature (ºC) -5+40 -5+40
Tropicalizzazione IEC:60068-2-30,60721-2-1 · ·
Electromagnetic compatibility IEC62271-1 · ·
  Fixed HD4 36kv circuit-breaker with 350mm pole centre distance:         Ir = 630-1250-1600A;              Isc = 16-20kA. Fixed HD4 36Kv circuit-breaker with 275mm pole centre distance:                            Ir =1250-1600A;                         Isc =25-31.5kA;
Ir =2000-2500A;                         Isc =20-25-31.5Ka.
  1. Rated normal current defined in free air
  2. Rated service value
  3. For these versions, with 275mm pole centre distance, special insulating partitions are provided(on request)
  4. For the dimensions of the insulating partitions(available on request), see the standardised table in chapter 5
  5. Operation sequence: O-0.3min-CO-3min-CO
  6. The second distance refers to the circuit-breaker with truck(available on request)
 
HD4 Gas Insulated Mv Circuit-Breakers up to: 40.5kv 3600A 50ka

ATTENTION:

1.The payment term: We accept TT,30% deposit and 70% balance against copy of BL.
2.The delivery time: Usually it will take about 15-20 days.
3.The standard of package: Usually use strong plywood case for protection.
4.The material of transformer: We have two types, one is with copper and another one is with aluminum. It depends on your requirement. In fact, those two have difference if normal work well. Only except the long life. Copper is better and also higher price.
5.The logo: If you have good quantity, it absolute no problem to do OEM.
6.Our market: our products are popular in Indonesia, Philippines, Russia, USA, Middle East and so on. Some of them are our regular customers and some of them are developing. We hope you can join us and make mutual benefit from our cooperation..
7.Warranty: in 12 month since BL date.

OUR SERVICE:

1.quick response in before sales period help you got order.
2.excellent service in production time let you know each step we made.
3.reliable quality solve you after sale headache.
4.long period quality warranty ensure you can buy without hesitate.


WHY CHOOSE ROCKWELL:

1. One-stop supplier globally.
2. More than 10 years professional experiences in electrical appliance industry. 
3.We offer professional online technology support for perfecting your electrical solution free.
4. Experienced sales service and suggestion.
5. All the products with accessories under strict quality control and final inspection before shipping.
6. We can assure the powerful competitive price and reliable quality products.
7. Most competitive shipping rate from our own shipping forwarder.
8. Warranty assurance: 12 month
9. Whatever big or small order, we can provide you one-to-one service.  

CONTACT US:

Contact person: Mr. Chen Chengming
Tel:86-577-27869969
Mobile:86-18668777248
 HD4 Gas Insulated Mv Circuit-Breakers up to: 40.5kv 3600A 50ka


Your Best Choice for Electrical Appliances Industry!!!
Please leave an inquiry to know more details about Price , Packing ,Shipping and Discount.

 
HD4 Gas Insulated Mv Circuit-Breakers up to: 40.5kv 3600A 50ka

Send your message to this supplier

*From:
*To:
avatar Mr. Chen Chengming
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now

You Might Also Like

Contact Supplier

Diamond Member Since 2013

Suppliers with verified business licenses

Manufacturer/Factory & Trading Company
Year of Establishment
2008-12-08
Management System Certification
ISO9001:2015, ISO14001:2015, ISO45001:2018 certificate