Motorize operation load break switch
RPS Manual type operation load break switch is equipped with very simple and reliable mechanism with is operated by a single spring rotate type mechanism, which we call it manual type.
RPS motorize operation load break switch is a basic manual LBS with a additional a motor gear system. It can be drived by a electric control via a motor to instead of labor operation.
After add a additional motorized with control and relay protection components, communication module, it upgarde to remote control LBS / sectionalizer which able to achieve to link into SCADA or by a micro automation system.
It is a used for switching on/off on load line with E3 a 6000 times duty, and type tested under KEMA lab by IEC62271-103 standard.
The type LBS is now widely running over world.
· Summary
ROCKWILL® Electric strives to bring our customers the latest technology and competitive pricing and best service for distribution automatic.
RPS is an SF6-insulated, outdoor pole mounted load break switch family for overhead lines and specifically designed for use in modern remote controlled distribution automation systems. The RPS offers reliable maintenance free operation even in the most demanding climatic conditions including salt laden atmospheres, corrosive industrial pollution, snow and ice. It has excellent load breaking and fault making capacity and satisfies the isolation requirements specified for load break switch. The earthed metal tank prevents all possible leakage currents across an open switch. RPS can be manually operated or motor operated for local and remote electric control, upgraded.
·Service environment
1.Air temperature: Maximum temperature: +85ºC; Minimum temperature:-45ºC
Humidity: Monthly average humidity 95%; Daily average humidity 90% .
Altitude above sea level: Maximum installation altitude: 2500m or more higher.
Ambient air not apparently polluted by corrosive and flammable gas, vapor etc. No frequent violent shake
·Offering
With optional classes for rated current range:
--Type RPS 15, Rating6-20 kV with 400A, 16 kA up to 1250A, 20kA;
--Type RPS 27, Rating22-27 kV with 400A, 16 kA up to 1250A, 20kA;
--Type RPS 38, Rating30-40.5 kV with 400A, 16 kA up to 1250A, 20kA;
With optional classes for different grid application installation:
Section function (Section)
50 Instantaneous/Definite-Time Overcurrent(P.OC)
51 Phase Time-Overcurrent(P.Fast curve/P.Delay curve)
Overload (N.Fast curve/N.Delay curve)
50N Residual Ground Instantaneous/Definite-Time Overcurrent(G.OC)
51N Residual Ground Time-Overcurrent (G.Fast curve/G.Delay curve)
50SEF Sensitive Earth Fault (SEF)
51c Cold Load(Cold load)
TRSOTF Switch-Onto-Fault(SOTF)
59 Over Voltage(L.Over volt)
27 Under Voltage (L.Under volt)
Monitoring Functions:
Primary/Secondary Phases and Earth Currents
Direction
Primary/Secondary Line and Phase Voltages
Apparent Power and Power Factor
Real and Reactive Power
Historical Demand Record
Positive Phase Sequence Voltage & Current
Negative Phase Sequence Voltage & Current
Zero Phase Sequence Voltage
Frequency
Binary Input/Output status
Trip circuit healthy/failure
Time and date
Fault records
Event records
·Time-Overcurrent Curves
The following information describes the curve timing for the curve and time dial settings made for the time-overcurrent elements The time-overcurrent relay curves in conform to IEEE C37.112-1996 IEEE Standard Inverse-Time Characteristic Equations for Overcurrent Relays.
Creepage Distances of RPS
Terminal to ground creepage | 15kV BIL 95/110kV | 27kV BIL125/150kV | 38kV BIL 170/200kV |
Composite bushing | 564mm | 840mm | 1400mm |
Porcelain bushing | 556mm | 708mm | 1250mm |
·Current transformer and Voltage sensor
Part Number | RPS-15 | RPS-27 | RPS-38 | |||
Manual | Motorize | Manual | Motorize | Manual | Motorize | |
Current transformer | / | 3 | / | 3 | / | 3 |
Voltage sensor | / | 3/6 | / | 3/6 | / | 3/6 |
Note: Current transformers and voltage sensors can be customized according to requirements.
·Standards for reference
IEC 62271-1 IEC 62271-102 IEC 62271-103
High-voltage switchgear and controlgear. Part 103: switches for rated voltage above 1 kV up to and including 52 kV
Insulation level | ||||
Rated voltage | kV | 15 | 27 | 38 |
Power frequency withstand voltage, 50 Hz | ||||
- to earth and between phases | kV | 28 | 50 | 70 |
- across the isolating distance | kV | 32 | 60 | 80 |
Lightning impulse withstand voltage | ||||
- to earth and between phases | kV | 75 | 125 | 170 |
- across the isolating distance | kV | 85 | 145 | 195 |
Current ratings | ||||
Rated normal current | A | 400/630/800/1250 | ||
Mainly active load breaking current | A | 400/630/800/1250 | ||
Number of breaking operations CO | times | 400 | ||
Line-charging breaking current | A | 1 | 1.5 | 2 |
Cable-charging breaking current | A | 10 | 16 | 20 |
Earth fault breaking current | A | 50 | 50 | 130 |
Cable charging breaking current | ||||
under earth fault conditions | A | 28 | 28 | 80 |
No-load transformer breaking current | A | 20 | ||
Short-circuit ratings | ||||
Short-time withstand current, Ik | kA/s | 20 kA/4 s | 20 kA/4 s | 20 kA/4 s |
Peak withstand current | kA | 50 | 50 | 50 |
Short-circuit making current | kA | 50 | 50 | 50 |
Number of making operations | ||||
- main switch 50 kA (CL E3) | times | 5 | 5 | 5 |
- main switch 31.5 kA (CL E3) | times | 10 | 10 | 10 |
- earthing switch 50 kA (CL E2) | times | 3 | 3 | 3 |
- earthing switch 31.5 kA (CL E3) | times | 5 | 5 | 5 |
Ambient air temperature limits | -40°C...+60°C | |||
Mechanical endurance (number of CO operations) | ||||
- main switch | times | 5000 | 5000 | 5000 |
- earthing switch | times | 2000 | 2000 | 2000 |
Filling pressure (+20°C) | bar (abs) | 1.4-1.5 | 1.4-1.5 | 1.8-1.9 |
Alarm pressure (+20°C) | ||||
- density switch | bar (abs) | 1.2 | 1.2 | 1.65 |
- density gauge | bar (abs) | 1.2 | 1.2 | 1.6 |
- low gas lock-out mechanism | bar (abs) | 1.1 | 1.1 | 1.6 |
Weight | ||||
Composite bushing | kg | 115 | 125 | 135 |
Porcelain bushing | kg | 125 | 135 | 155 |
Motorize | Add 20kg | |||
Degree of protection of the mechanism box | IP67 |