Customization: | Available |
---|---|
Certification: | ISO9001 |
Shell Material: | Expoxy |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Rated voltage (kV) | 7.2 | 12 | 17.5 | 24 | |
Insulation level | |||||
50 Hz, 1 mn (kV rms) |
Insulation | 20 | 28 | 38 | 50 |
Isolation | 23 | 32 | 45 | 60 | |
1.2/50μs (kV peak) |
Insulation | 60 | 75 | 95 | 125 |
Isolation | 70 | 85 | 110 | 145 | |
Breaking capacity | |||||
Transformer off load (A) | 16 | ||||
Cables off load (A) | 31.5 | ||||
Short-time withstand current (kA.1 s) |
25 | 630 - 1250 A | |||
20 | 630 - 1250 A | ||||
16 | 630 - 1250 A | ||||
12.5 | 400 - 630 - 1250 A | ||||
The making capacity is equal to 2.5 times the short-time withstand current. * 60 kV peak for the CRM unit. |
|||||
Maximum breaking capacity | |||||
Rated voltage (kV) | 7.2 | 12 | 17.5 | 24 | |
Units | |||||
IM, IMC, IMB, NSM-cables, NSM-busbars |
630 A - 800 A* | ||||
PM, QM, QMC, QMB | 25 kA | 20 kA | |||
CRM | 10 kA | 8 kA | |||
CRM with fuses | 25 kA | ||||
SF6 circuit breaker range: | |||||
DM1-A, DM1-D, DM1-W, DM1-Z, DM1-S, DM2 | 25 kA | 20 kA | |||
Vacuum circuit breaker range: | |||||
DMV-A, DMV-D, DMV-S | 25 kA | 20 kA |