Rated voltage (kV) | 7.2 | 12 | 17.5 | 24 | |
Insulation level | |||||
50 Hz, 1 mn | Insulation | 20 | 28 | 38 | 50 |
(kV rms) | Isolation | 23 | 32 | 45 | 60 |
1.2/50μs | Insulation | 60 | 75* | 95 | 125 |
(kV peak) | Isolation | 70 | 85 | 110 | 145 |
Breaking capacity | |||||
Transformer off load (A) | 16 | ||||
Cables off load (A) | 31.5 | ||||
Short-time withstand current | 25 | 630 - 1250 A | |||
(kA.1 s) | 20 | 630 - 1250 A | |||
16 | 630 - 1250 A | ||||
12.5 | 400 - 630 - 1250 A |
Rated voltage (kV) | 7.2 | 12 | 17.5 | 24 | ||
Units | ||||||
IM, IMC, IMB, | 630 A - 800 A* | |||||
NSM-cables, NSM-busbars | ||||||
PM, QM, QMC, QMB | 25 kA | 20 kA | ||||
CRM | 10 kA | 8 kA | ||||
CRM with fuses | 25 kA | |||||
SF6 circuit breaker range: | ||||||
DM1-A, DM1-D, DM1-W, DM1-Z, DM1-S, DM2 | 25 kA | 20 kA | ||||
Vacuum circuit breaker range: | ||||||