• 10-35kv Electric Furnace Transformer/Electric Arc Furnace Transformer/Power Supply Transformer Furnace Transformer
  • 10-35kv Electric Furnace Transformer/Electric Arc Furnace Transformer/Power Supply Transformer Furnace Transformer
  • 10-35kv Electric Furnace Transformer/Electric Arc Furnace Transformer/Power Supply Transformer Furnace Transformer
  • 10-35kv Electric Furnace Transformer/Electric Arc Furnace Transformer/Power Supply Transformer Furnace Transformer
  • 10-35kv Electric Furnace Transformer/Electric Arc Furnace Transformer/Power Supply Transformer Furnace Transformer
  • 10-35kv Electric Furnace Transformer/Electric Arc Furnace Transformer/Power Supply Transformer Furnace Transformer

10-35kv Electric Furnace Transformer/Electric Arc Furnace Transformer/Power Supply Transformer Furnace Transformer

Application: Power
Phase: Three
Core: Core-type Transformer
Cooling Method: Oil-immersed Type Transformer
Winding Type: Multi-winding Transformer
Certification: ISO9001-2000, ISO9001, CCC
Customization:
Diamond Member Since 2013

Suppliers with verified business licenses

Manufacturer/Factory & Trading Company

Basic Info.

Model NO.
H/HJ/HZ/HC/HK/HG
Usage
Power Transformer
Frequency Characteristics
Power Frequency
Shape of Core
Ring
Brand
Rockwell
Rated Voltage
10-35kv
Frequency
50Hz
Insulated Oil
High Quality Grade Mineral Oil
Transport Package
Wooden Packing
Trademark
Rockwell
Origin
China
HS Code
8504231100
Production Capacity
500

Product Description

Electric furnace transformer

Feature


An electric furnace transformer is used to supply power to an electric furnace, which lowers the high voltage to the furnace-required lower voltage.

Its type varies with the type of electric furnace, so the transformer has many types. Currently we manufacture following types: Arc furnace transformers used for steel-smelting (including load-ratio voltage regulator type, no-load voltage regulator type, and built-in reactor type); blast furnace transformers used for smelting of iron alloy, silicides, calcium carbide(single phase, three phase, load ratio voltage regulator and no-load voltage regulator). All energy-saving products with low power loss. The cooling modes are self-cooling mode, forced water cooling mode, etc. and we can also provide the special transformer by the customer's demands.

The model of the electric furnace transformer is expressed as follows:

10-35kv Electric Furnace Transformer/Electric Arc Furnace Transformer/Power Supply Transformer Furnace Transformer
Meaning: H-steel smelting arc furnace, HJ-ladle fining furnace, HZ-electroslag furnace, HC-calcium carbide furnace, HK-blast furnace, HG-industrial furnace
Number of phase: D-single phases, S-three phases
Type of cooling devices: oil immersed self-coiling- air cooling F, water cooling S
Way of oil circulation: natural circulation, forced oil circulation P 
Way of voltage regulation: non-excitation voltage regulation, load ratio voltage regulation
Built-in accessories: flux leakage changing group-,built in reactor K
Rated capacity: kVA
Voltage class: KV

Non-excitation-tap-changing arc furnace transformer technical data

 
Rated power (kVA) With series reactor
Primary
Voltage
(kV)
secondary
Voltage
(kV)

Rated secondary current
(A) 
Type of taping Vector group Short
Circuit
Impedance
(%)
Series reactor No-load loss
(kW)
On-load
Loss
(kW)
No-load
Current
(%)
Rated power
(kvar)
Reactance
Voltage
Drop(%)
630
800
1000
6
6.3
10
10.5
11
200
170
116
98
1819
2609
2887
no-load
Tap
changing
Dd0
Dy11
8-9
 
 
 
 
 
 
 
 
 
 
 
7-8
120
150
190
19 2.4
2.7
3.1
8.6
11.0
14.0
3.0
2.9
2.9
1250
1600
2000
210
180
121
104
3437
4399
5499
200
260
320
16 3.6
4.1
4.6
17.5
22.0
27.0
2.6
2.5
2.4
2500
3150
220
190
127
110
6561
8267
280
350
11.2 5.2
6.0
32.0
39.0
2.3
2.2
4000
5000
240
210
139
121
9623
12028
340
360
8.5 7.6
9.4
46.0
54.0
2.1
2.0
6300
8000
260
240
210
139
13900
17765
430
460
5.7 11.8
15.0
63.0
74.0
1.9
1.8

Main technical data for arc furnace transformer with on-load-tap-changing
 
Rated power (kVA) Primary
Voltage
(kV)
Secondary
Voltage
(V)
 
Secondary
Step voltage
(V) 
Rated secondary
Current(A)
Regulation
Voltage step
Vector group Short-
circuit 
Impedance(%)
Cooling
method
 
Invariablenes
power
Invariablenes
current
10000 35
66
280-240 240-100 10 24056 19(5,14)
5 steps invariableness
Power
14 steps
Invariableness 
current
Dd0
Yd11
Ynd11
7-8 OFWFOFAF
12500 314-270 270-116 11 26729
16000 353-305 305-137 12 30287 6-7
(35kV)
7.5-8.5
(66,110kV)
 
20000 35
66
110
392-340 340-158 13 33962
25000 436-380 380-184 14 37984
31500 489-425 425-201 16 42792
40000 547-475 475-223 18 48619
50000 610-530 530-250 20 54467
63000 673-585 585-277 22 62176
80000 760-660 660-310 25 69982

Electroslag furnace transformer technical parameters
type Rated power
(kVA)
Rated voltage Vector group
Primary
(kV)
Secondary
(V)
HZD-400/10 400 10 60/55/51/47/44 li0
HZDZ-500/10 500 10 70/67/64/62/60/58/56/53/50 li0
HZD-630/10 630 10 70/63.2/57.6/53/49/45.6/42.6/40 li0
HZD-700/10 700 10 70/64/56/52/47 li0
HZDZ-800/10 800 10 87/83/79/77/75/73/70/65/60 li0
HZD-1000/10 1000 10 80/75/72.5/70/67.5/65/60/55/50 li0
HTZ-1118/6.3 1118 6.3 260/238/216/194/172/150/128/106/84/62/40 YaT
HTZ-1474/6.3 1474 6.3 275/250/225/200/175/150/125/100/8060 YaT
HZDSP-1620/10 1620 10 90-55(8 step) li0
HZDSPZ-1620/6.3 1620 6.3 90-45.2(27 step) li0
HSZ-1794/6.3 1794 6.3 260/238/216/194/172/150/128/106/84/62/40 Ya0,Dd0
HZDSPZ-2400/10 2400 10 96-56(18 step) li0

Ladle-furnace transformer technical data
type Rated power
(kVA)
Rated voltage Vector group
Primary
(kV)
Secondary
(V)
HJSSP-2400/10 2400 10 200/190/110/104/180 D-Yd0-11
HJSSP-2400/11 2400 11 210/196/113/100/173 D-Yd0-11
HJSSP-2800/10 2800 10 190/175/160/110/101/92.5 D-Yd0-11
HJSSP-3150/10 3150 10 210/195/180/165/150 Yd11
HJSSP-3200/35 3200 35 210/195/170/121/112.5/98 D-Yd0-11
HJSSP-4000/10 4000 10 210/195/180/155 Dd0
HJSSP-5000/11 5000 10 210/195/180/165/121 D-Yd0-11
HJSSP-6300/35 6300 35 215/200/185/170/155 Yd11
HJSSP-7000/10 7000 10 216/202/188/175/161 Dd0
HJSSP-7000/35 7000 35 220/205/191/175/160/145 Yd11
HJSSP-10000/10 10000 10 240/210/180/160/139/121 D-Yd0-11
HJSSP-12000/35 12000 35 260-150 13 level Yd11
HJSSP-13000/35 13000 35 240-150 19 level Yd11
HJSSP-18000/35 18000 35 344-231 13 level Yd11

Main technical data of 10KV Arc furnace transformer for steel making
type Rated power
(kVA)
Vector group Primary
Voltage
(kV)
Secondary
Voltage
(V)
Regulation voltage
(V)
Type of taping Short-circuit
Impedance
(%)
No-load 
Loss
(W)
On-load
Loss
(W)
HS-650/10 650 D-y,d0-11 10 130-75 5 No load 20 1.9 10
HS-1250/10 1250 D-y,d0-11 10 210-160 5 No load 21 2.9 15.7
HS-1600/10 1600 Yd11 10 85-65 5 No load 6.0 5.1 17.4
HSZ-2000/10 2000 Yd11 10 300-140 15 On load 4/6 5.3 33.7
HSSPK-2500/10 2500 D-y,d0-11 10 220-110 6 No load electric 21/9 5.4 32.7
HS-3000/10 3000 D-y,d0-11 10 220-110 5 No load electric 19/9 5.2 26.2
HSSP-3200/10 3200 Dd0 10 240-104 5 No load electric 18/7 7.7 40.9
HSSP-4200/10 4200 D-y,d0-11 10 240-160 5 No load electric 18.5 7.3 33.2
HSSP-5500/6 5500 Dd0 6 212-150 5 No load electric 8 10.1 47
HSSPK-5500/6 5500 Dd0 6 260-139 8 No load electric 9 7.5 60
HSSP-6300/6 6300 Yd11 6 207-158 5 No load electric 7.5 8.5 58.2
HJSSP-7500/10 7500 D-y,d0-11 10 240-140 6 No load electric 6.4 10.7 78.2
HSSPZ-8000/10.5 8000 Yd11 10.5 300-140 17 On load 7 11.8 99.8
HUSSPZ-8000/10 8000 Dd0 10 240-149 9 On load 7.5 9.8 76.8
HSSPZ-9000/6 9000 Yd11 6 240-85 17 On load 7 13.7 121.6
HSSP-12500/10 12500 Dd0 10 325-166 11 No load electric 8 12.4 145.7
HJSSPZ-14000/10 14000 Dd0 10 325-205 13 On load 6.5 13.2 134.6

Main technical data of 35KV Arc furnace transformer for steel making
 
type Rated power
(kVA)
Vector group Primary
Voltage
(kV)
Secondary
Voltage
(V)
Regulation voltage
(V)
Type of taping Short-circuit
Impedance
(%)
No-load 
Loss
(W)
On-load
Loss
(W)
HSSPZ-1500/35 1500 Yd11 35 290-157 10 On load 5.5 2.6 23
HSSP-3200/35 3200 D-Y, d0-11 35 240-138 4 No load electric 7 5.3 41.1
HSSPL-3200/35 3200 D-Y, d0-11 35 240-138 5 No load electric 18.65 5.3 91.1
HJSSP-5000/35 5000 Yd11 35 212-155 5 No load electric 7.5 9.3 55
HJSSP-5500/35 5500 Yd11 35 240-130 6 No load electric 7.5 9.1 52.5
HJSSP-7000/35 7000 Yd11 35 240-140 8 No load electric 7 9.4 77
HJSSPZ-9000/35 9000 Yd11 35 239-163 9 On load 6.5 11.6 97
HSSP-9000/35 9000 Yd11 35 320-180 8 No load electric 8.5 11 116
HJSSPZ-10000/35 10000 Yd11 35 260-188 9 On load 6 17.2 187
HSSPZ-10000/35 10000 Yd11 35 300-160 13 On load 8.5 12 97
HSSPZ-12500/35 12500 Yd11 35 250-150 9 On load 6.5 19.7 134
HSSP-12500/35 12500 Yd11 35 340-195 11 No load electric 9 13.9 154
HSSP-15000/35 15000 D-Y, d0-11 35 353-160 8 No load electric 8 20 107
HSSPZ-16000/35 16000 Yd11 35 375-200 15 On load 8 16.4 161
HJSSPZ-16000/35 16000 Yd11 35 310-190 13 On load 7 19.2 195.6
HSSPZ-20000/35 20000 Yd11 35 400-270 13 On load 7 20.7 207.7
HJSSPZ-20000/35 20000 Dd0 35 320-170 11 On load 6.5 30.4 313.6
HSSPZ-25000/35 25000 Yd11 35 509-302 13 On load 7.5 28.5 272.6

Blast furnace, calcium carbide furnace transformer technical parameters
type Rated power
(kVA)
Vector group Primary
Voltage
(kV)
Secondary
Voltage
(V)
Regulation voltage
(V)
Type of taping Short-circuit
Impedance
(%)
No-load
Loss
(W)
On-load
Loss
(W)
HKS-1000/10 1000 Dd0 10 72-64 5 No load 6.5 3.02 14
HKS-1600/10 1600 D-Y, d0-11 10 345-199 8 No load 7 4.06 18.26
HKS-3000/10 3000 Dd0 10 126-70 8 No load 7 5.33 45
HKSSP-3150/10 3150 Yd11 10 230-130 5 No load 7 6.36 31.02
HKSSPZ-4000/6 4000 Yd11 6 200-59 15 On load 4.5 11.2 37
HKSSP-4500/10 4500 Dd0 10 120-92 8 No load 6.5 8.33 48.82
HKSSP-6000/10 6000 Yd11 10 140-100 7 No load 8 9.2 66.6
HKSSPZ-6300/10 63000 Dd0 10 134-110 9 On load 6 7.7 66.5
HKSSP-3200/35 3200 Yd11 35 230-150 5 No load 7 7.11 40.13
HKSSP-5600/35 5600 Yd11 35 270-160 7 No load 6 8.77 53.2
HKSSP-6300/35 6300 Yd11 35 140-100 9 No load 7.5 9.01 69.87
HKSSP-10000/35 10000 Yd11 35 350-170 9 No load 7 10.1 79.7
HKSSP-12500/35 12500 Yd11 35 365-153 5 No load 7 16.6 95
HCS-1000/10 1000 Yd11 10 80-60 5 No load 6 3.73 12.2
HCS-1800/10 1800 Yd11 10 105-75 5 No load 7 5.4 28.8
HCSSP-3000/10 3000 Dd0 10 80-108 8 No load 6.5 3.9 65.5
HCSSP-5000/10 5000 Yd11 10 120-95 5 No load 6.5 10.23 44.6
HCSSP-8000/10 8000 Dd0 10 128-112 5 No load 7 11.9 94
HCSSP-6300/35 6300 Yd11 35 126-98 8 No load 8 8.1 87.6
HCSSPZ-10000/35 10000 D-Y, d0-11 35 164-98 19 On load 7 16.8 91.35
HCSSP-12500/35 12500 Dd0 35 165-126 13 No load 6.5 16.8 112.1

 

10-35kv Electric Furnace Transformer/Electric Arc Furnace Transformer/Power Supply Transformer Furnace Transformer
10-35kv Electric Furnace Transformer/Electric Arc Furnace Transformer/Power Supply Transformer Furnace Transformer

10-35kv Electric Furnace Transformer/Electric Arc Furnace Transformer/Power Supply Transformer Furnace Transformer
ATTENTION:

1.The payment term: We accept TT,30% deposit and 70% balance against copy of BL.
2.The delivery time: Usually it will take about 15-20 days.
3.The standard of package: Usually use strong plywood case for protection.
4.The material of transformer: We have two types, one is with copper and another one is with aluminum. It depends on your requirement. In fact, those two have difference if normal work well. Only except the long life. Copper is better and also higher price.
5.The logo: If you have good quantity, it absolute no problem to do OEM.
6.Our market: our products are popular in Indonesia, Philippines, Russia, USA, Middle East and so on. Some of them are our regular customers and some of them are developing. We hope you can join us and make mutual benefit from our cooperation..
7.Warranty: in 12 month since BL date.

OUR SERVICE:

1.quick response in before sales period help you got order.
2.excellent service in production time let you know each step we made.
3.reliable quality solve you after sale headache.
4.long period quality warranty ensure you can buy without hesitate.


WHY CHOOSE ROCKWELL:

1. One-stop supplier globally.
2. More than 10 years professional experiences in electrical appliance industry.
3.We offer professional online technology support for perfecting your electrical solution free.
4. Experienced sales service and suggestion.
5. All the products with accessories under strict quality control and final inspection before shipping.
6. We can assure the powerful competitive price and reliable quality products.
7. Most competitive shipping rate from our own shipping forwarder.
8. Warranty assurance: 12 month
9. Whatever big or small order, we can provide you one-to-one service. 

CONTACT US:

Contact person: Mr. Chen Chengming
Tel:86-577-27869969
Mobile:86-18668777248
10-35kv Electric Furnace Transformer/Electric Arc Furnace Transformer/Power Supply Transformer Furnace Transformer
 
Your Best Choice for Electrical Appliances Industry!!!
Please leave an inquiry to know more details about Price , Packing ,Shipping and Discount.

10-35kv Electric Furnace Transformer/Electric Arc Furnace Transformer/Power Supply Transformer Furnace Transformer
 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now

You Might Also Like

Diamond Member Since 2013

Suppliers with verified business licenses

Manufacturer/Factory & Trading Company
Year of Establishment
2008-12-08
Management System Certification
ISO9001:2015, ISO14001:2015, ISO45001:2018 certificate